Reading time: approx. 5 minutes
The alarm center displays the message “Ethernet fault NSL protocol”.
The message appears as soon as the “NSL Reporting” function is generally enabled and the alarm center detects a disruption in the communication channel to an emergency call and service control center (“NSL” for short).
You as the installer must then:
- either deactivate the “NSL Reporting” function (e.g. directly after initial commissioning, if desired),
- or check whether the priority of the communication channels is set correctly,
- or check whether there is a fault in the connected NSL or on the way there (e.g. in the router).
Deactivate the “NSL Reporting” function
If no transmission of events to an alarm receiving center (AES) or emergency call and service control center (NSL) is desired , as the installer, block “NSL Reporting”.
- Log in as an installer , e.g. using the Secvest web interface .
- Go to Installer Mode > Communication > NSL Reporting .
This will bring up the “NSL Reporting” screen.
- Under “Call mode” select the option “Locked” .
In individual cases, the Secvest still displays the last message that appeared. There are two options available to delete or reset this message:
Option A) Restart the system (all settings/configurations, e.g. taught-in detectors, etc., are retained).
info
During the restart, Secvest creates an SSL certificate. This can take a few minutes. The message “Network initialization, please wait ...” appears.
When you restart, Secvest automatically logs you out of the user menu. If you want to continue working there, log in again as usual with your user name and password.
Option B) Optionally, proceed step by step as described below:
- First exit the installer mode.
- Then log in again as an installer using the local user interface or the Secvest web interface.
- Go to Installer Mode > Communication > NSL Reporting > Call Mode .
- Select the option “Enabled”.
- Exit the installer mode again.
- Log in again as an installer using the local user interface or the Secvest web interface.
- Go to Installer Mode > Communication > NSL Reporting > Call Mode .
- Select the “Locked” option.
In both cases the message disappears and the “NSL Reporting” function is deactivated .
Set priority communication channels
If you want events to be transmitted to an AES/NSL (= alarm receiving center or emergency call and service control center) and it is basically configured correctly, you may still need to set the priority of the transmission path correctly.
- Log in as an installer , e.g. using the Secvest web interface .
- Go to Installer Mode > Communication > NSL Reporting > Communication Priority .
This will bring up a window.
Communication Priority window
- For “Ethernet” set “1” or, depending on the desired order/priority , “2” or “3” if you also use “PSTN” and/or “GSM”.
- Set unused communication channels to “No” .
Now the priority is set as desired and the message disappears .
Notice
We recommend testing “NSL Reporting” after each configuration/change and also regularly during normal operation.
Contact AESAG Support
More Articles
- Latest firmware, software, apps and utilities
- How do I create a “Level 4 user”?
- How do I access the Secvest via the Internet using the ABUS server?
- How do I restart the Secvest alarm panel?
- How do I perform a remote update using the Level 4 user?
- How do I set up the Secvest GSM module?
- Get to know the basic controls of Secvest: Local user interface and web interface
- Listenelement
- How do I activate and deactivate Secvest?
- How do I change my code or username?
- How do I perform a code reset?
- How do I access the Secvest via the Internet using the ABUS server?
- How do I create a backup of the configuration?
- How do I put the ABUS Secvest wireless alarm system into operation?
- How do I adjust the volume?
- Which optional controls are available for the Secvest?
- Where does it say which firmware version is available?
- ListenelementWhat causes an alarm?
- How do I turn off the alarm?
- https://www.aesag.ch/en/content/36-what-does-the-message-ethernet-error-nsl-protocol-mean